KYN61 40.5KV 1250A 1600A 2000A Armoured Removable High Voltage Switchgear HV Complete Set

Short Description:

KYN61-40.5(Z) armored removable AC metal-enclosed switchgear) is a complete set of indoor power distribution devices with three-phase AC volume of 50Hz and rated voltage of 40.5kV.


Product Detail

Product Tags

Product Description

KYN61-40.5(Z) armored removable AC metal-enclosed switchgear) is a complete set of indoor power distribution devices with three-phase AC volume of 50Hz and rated voltage of 40.5kV. As power plants, substations, industrial and mining enterprises to receive and distribute electrical energy, control, protect and monitor the impact on circuits, and can also be used in places that operate frequently. The switchgear conforms to GB3906-2006, GB/T11022-1999 and DL/T 404-2007 standards.

形象8

Model Description

型号含义24_看图王
形象3

Product technical parameters and External dimensions

Vacuum circuit breaker technical parameters

断路器技术参数

 Spring-operated mechanical technical parameters

弹黄操动技术参数

 Vacuum switch cabinet technical parameters

开关柜技术参数

开关柜外形尺寸
形象9

Product structure features

1:The cabinet structure adopts the assembled type, and the circuit breaker adopts the handcart floor type structure;
2: The new composite insulation vacuum circuit breaker is adopted, which has the characteristics of simple replacement and good compatibility;
3:the screw nut feeding mechanism installed in the handcart frame, The handcart can be easily moved to prevent misoperation and its structural damage;
4:All operations can be carried out with the cabinet door closed;
5: the main switch, handcart, and switch cabinet door interlock adopt forced mechanical locking, which conforms to the "five-proof" function ;
6:Sufficient space in the cable room to connect multiple cables;
7:Quick grounding switch for grounding and closing short-circuit circuits;
8:External enclosure protection grade IP3X, handcart door open state, protection grade IP2X;
9:The product conforms to GB3906-2006, DL/ T 404-2007 and refer to the international standard IEC298.

形象7

Environment condition

1. Ambient air temperature: -5~+40 and the average temperature should not exceed +35 in 24h.
2. Install and use indoors. Altitude above sea level for operation site should not exceed 2000M.
3. Relative humidity should not exceed 50% at max temperature +40. Higher relative humidity is allowed at lower temperature. Ex. 90% at +20. But in view of the temperature change, it is possible that moderate dews will produce casually.
4. Installation gradient not exceed 5.
5. Install in the places without fierce vibration and shock and the sites insufficient to erode the electrical components.
6. Any specific requirement, consult with manufactory.